Chigo Split Floor-Standing Air Conditioner User Manual

Browse online or download User Manual for Split-system air conditioners Chigo Split Floor-Standing Air Conditioner. Failure code manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 13
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
1
Failure code manual
content
一、wall split AC series………… …………………………………………2
二、floor standing AC series………….……………………………………4
三、portable AC series…………..…………………………………………5
四、dehumidifer……………………………………………………………6
五、DC inverter single split series…………................................................7
六、DC inverter multi-split series…………………………………………10
Page view 0
1 2 3 4 5 6 ... 12 13

Summary of Contents

Page 1 - Failure code manual

1Failure code manual content 一、wall split AC series………… …………………………………………2 二、floor standing AC series………….……………………………………4 三、portable AC series…………..……

Page 2 - 一、wall split AC series

10protection 2、Check whether the sensor, connecting wire of the sensor and the detection circuit are abnormal. P5 5 light over heat of compressor t

Page 3

113、 When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced. F3 outlet

Page 4 - 二、floor standing AC serial

12control should be replaced when it is abnormal. P4 discharge temp. of compressor too high, outside ambient temp. too high, temp. switch of compress

Page 6 - 四、dehumidifer series

2一、wall split AC series LED lamp display code explain code explain failure The reason of fault and solution DF display at on state flicker 1/1 SE

Page 7

3it is damaged. 6、If the above items are normal, the electric control board should be replaced. E5 PG motor display at off state flicker 5/7 SEC dis

Page 8

4二、floor standing AC serial LED lamp display code explain code explain failure The reason of fault and solution E2 display at off state flicker 2

Page 9

5the unit is running. 3、 Check whether the indoor and outdoor wiring is right; when it is wrong, connect them again according to the circuit diagram

Page 10

6components or integrated circuit is damaged, the electric control board should be replaced. E4 display at off state abnormal protection 1、Check wh

Page 11

73、 When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control board should be replaced. continuous

Page 12

8unit fault and socket is well, making sure well contact. 2、Check whether the indoor motor has damaged, the motor should be replaced when it is damag

Page 13

9board, repair it if there is any above. 3、When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric contr